The Journal of Process Control (JPC) version of our paper, "Split parallel control – a little known control structure" by Forsman, Adlouni and Skogestad (2026), is now published! Article link: https://authors.elsevier.com/sd/article/S0959-1524(26)00274-X Also see: https://skoge.folk.ntnu.no/publications/2026/ The paper considers the case where we use multiple inputs (u1, u2, ...) to control one output (y), but ideally we want to use only one input at a time. An example is room temperature (y) control with both heating (u1) and cooling (u2). The classical solution is split-range control, using a single controller. In this paper, we consider the less common alternative (at least in academia) of split-parallel control, using multiple separate controllers (for u1 and u2) with different setpoints (r1 and r2). For example, we may use r1 = 21°C for heating (mostly active in winter) and r2 = 23°C for cooling (mostly active in summer). Many other practical applications are discussed in the paper. The paper is an extended version of our IFAC DYCOPS conference paper presented in Bratislava in June 2025. The main extension is that we distinguish between four operating regions. Region 1: Only u1 (heating) is used to control y at setpoint r1. Region 2: Only u2 (cooling) is used to control y at setpoint r2. These two regions are partially constrained: u2 is at its lower constraint (no cooling) in Region 1, and u1 is at its lower constraint (no heating) in Region 2. With split-range control, there is a direct transition between Regions 1 and 2. However, with split-parallel control, the transition occurs through either Region 3 or Region 4. Region 3: A fully constrained, "open-loop" transition (where both heating and cooling are off). This is more likely with a large setpoint separation |r1 − r2|. Region 4: An unconstrained transition where both u1 (heating) and u2 (cooling) are competing to control y (temperature), but at different setpoints r1 and r2. This is more likely with a small setpoint separation. As one might expect, some interesting things can happen in Region 4. First, with integral action in both controllers, the competition leads to an internal instability that drives the inputs (u1 and u2) towards their constraints, eventually ending the transition. However, during thw transition, we get a "boosted" response with improved control of y (temperature). This may be followed by a "limbo" period, where y is "stuck" at an intermediate value between r1 and r2. The limbo period can be shortened or avoided by increasing the setpoint separation. Finally, there is a theoretical possibility of instability in the form of limit cycles in Region 4, although this seems unlikely with reasonably tuned controllers.